Prime Power : | 560kW / 700kVA 415 Volts 980Amps |
Standby Power : | 616kW / 770kVA |
Power Factor : | 0.8 |
Phase Voltage : | Three Phase 415 Volt |
Frequency : | 50 Hertz - Electronic Speed Controlled |
Engine : | CUMMINS Diesel 6 Cylinder NTA855-G2A + NTA855-G2A |
RPM : | 1500/min |
Cooling Method : | Water Cooled - Rated For Australia's North |
Alternator : | STAMFORD Three Phase 4 Pole Brushless HCI444E + HCI444E |
Starter System : | 24 volt Electric - Batteries Included |
Controller : | Comap IG200 IL3 Synchronizable |
2 Wire / Remote Start Capable
|
|
Over Temperature Protection
|
|
Over Current Protection
|
|
Low Oil Protection
|
|
Safety Systems : | Battery Isolators |
Emergency Stop | |
Failsafe Shutdown Fuel Solenoid | |
Noise Level : | 75 dB at 7 metres |
Fuel Tank Capacity : | 1000 Litres + 1000 Litres (-/c Fuel Gauge) |
Running Time : | 14 Hours Continuous (prime load) |
Fuel Consumption : | 144 Litres/Hour (prime load) |
Chassis Enclosure : | Lockable |
Sound Deadening Throughout | |
Weather Resistant Powder Coating | |
Stainless Steel Fittings | |
External Use | |
Mine Site Ready Bunding : | Yes |
ATS (Mains Failure) : | Easy Connect Plug (ATS Box Optional) |
Hardwire Terminals : | Yes |
RCD : | Australian Standard (IP67 Enclosed) |
Options : | Automatic Start Systems |
GSM
|
|
Timer
|
|
Synchronization
|
|
Wireless Remote
|
|
Solar System Compatible (Majority)
|
|
ATS (Mains Failure Detection / Auto Transfer Switch)
|
|
Minespec Padlockable Battery Isolator | |
Weight : | 4380 kg + 4380 kg |
Dimensions : |
395L x 160W x 230H cm + 395L x 160W x 230H cm |