Specifications

Prime Power : 560kW / 700kVA 415 Volts 980Amps
Standby Power : 616kW / 770kVA
Power Factor : 0.8
Phase Voltage : Three Phase 415 Volt
Frequency : 50 Hertz - Electronic Speed Controlled
Engine : CUMMINS Diesel 6 Cylinder NTA855-G2A + NTA855-G2A
RPM : 1500/min
Cooling Method : Water Cooled - Rated For Australia's North
Alternator : STAMFORD Three Phase 4 Pole Brushless HCI444E + HCI444E
Starter System : 24 volt Electric - Batteries Included
Controller : Comap IG200 IL3 Synchronizable
 
2 Wire / Remote Start Capable
 
Over Temperature Protection
 
Over Current Protection
 
Low Oil Protection
Safety Systems : Battery Isolators
  Emergency Stop
  Failsafe Shutdown Fuel Solenoid
Noise Level : 75 dB at 7 metres
Fuel Tank Capacity : 1000 Litres + 1000 Litres (-/c Fuel Gauge)
Running Time : 14 Hours Continuous (prime load)
Fuel Consumption : 144 Litres/Hour (prime load)
Chassis Enclosure : Lockable
  Sound Deadening Throughout
  Weather Resistant Powder Coating
  Stainless Steel Fittings
  External Use
Mine Site Ready Bunding : Yes
ATS (Mains Failure) : Easy Connect Plug (ATS Box Optional)
Hardwire Terminals : Yes
RCD : Australian Standard (IP67 Enclosed)
Options : Automatic Start Systems
 
GSM
 
Timer
 
Synchronization
 
Wireless Remote
 
Solar System Compatible (Majority)
 
ATS (Mains Failure Detection / Auto Transfer Switch)
  Minespec Padlockable Battery Isolator
Weight : 4380 kg + 4380 kg
Dimensions :

395L x 160W x 230H cm + 395L x 160W x 230H cm